SUP-ST500 Head Mounted Smart Temperature transmitter can be used with multiple sensor type [Resistance Thermometer(RTD),Thermocouple (TC)] inputs, is simple to install with improved measurement accuracy over wire-direct solutions.
Input signal: Resistance temperature detector (RTD), thermocouple (TC), and linear resistance.
Output: 4-20mA
Power supply: DC12-40V
Response time: Reach to 90% of the final value for 1s
Temperature transmitters are widely used in various industries for temperature measurement and control applications. They are highly accurate, reliable, and offer several advantages over other temperature measuring instruments. Some of the key features and advantages of temperature transmitters include:
Some specific applications of temperature transmitters include:
| Model | Type | Measurement scope | Minimum measurement scope | Accuracy |
|---|---|---|---|---|
| Resistance temperature detector (RTD) | Pt100 | -200~850℃ | 20℃ | ±0.2%/±0.4℃ |
| Cu50 | -50~150℃ | 20℃ | ±1.0%/±1.0℃ | |
| Thermocouple (TC) | B | 400~1820℃ | 500℃ | ±0.1%/±1.5℃ |
| E | -100~1000℃ | 50℃ | ±0.1%/±0.5℃ | |
| J | -100~1200℃ | 50℃ | ±0.1%/±0.5℃ | |
| K | -180~1372℃ | 50℃ | ±0.1%/±0.5℃ | |
| N | -180~1300℃ | 50℃ | ±0.1%/±0.5℃ | |
| R | -50~1768℃ | 500℃ | ±0.1%/±1.5℃ | |
| S | -50~1768℃ | 500℃ | ±0.1%/±1.5℃ | |
| T | -200~400℃ | 50℃ | ±0.1%/±0.5℃ | |
| Wre3-25 | 0~2315℃ | 500℃ | ±0.1%/±1.5℃ | |
| Wre5-26 | 0~2310℃ | 500℃ | ±0.1%/±1.5℃ |
| Input | |
|---|---|
| Input signal | Resistance temperature detector (RTD), thermocouple (TC), and linear resistance. |
| Cold-junction compensation temperature scope | -20~60℃ |
| Output | |
| Output signal | 4–20 mA |
| Load resistance | RL ≤ (U-10)/0.021 |
| Output current of upper and lower limit overflow alarm | IH = 21 mA, IL = 3.8 mA |
| Power supply | |
| Power supply | (12–40) VDC |
| Other parameters | |
| Response time | Reach to 90% of the final value for 1s |
| Used environmental temperature | -40~80℃ |
| Storage temperature | -40~100℃ |
| Vibration resistance | 4g/2~150Hz |
| Electromagnetic compatibility | Conform to GB/T18268 industrial equipment application requirements (IEC 61326-1) |
Characteristics Features 1. Full port, outside...