McFlow

K-G60 Fixed Gas Detector/Transmitter with Temperature compensation for gas

Characteristics

Target gas: Combustible gases and Toxice gases

Sample manner: Natural diffusion

Unit: %LEL, ppm, %VOL

Response time: <20s

Load resistance (4~20)mA:  ≤250 Ω

Accuracy: F.S.±3%

Repeatability: F.S.±1%

Working voltage: DC24V±15%

Product Categories

Products Menu

● High sensitivity and long life    

● Low drift and reliable performance    

● Self-check of sensor fault

● LCD display,menu operation    

● Temperature compensation   

● Explosion proof design    

● Easy to install    

● Can be worked stand alone    

● DC24V external power optional  

● 433Hz wifi optional    

● Romote control

● No need to calibrate

Gas Detector Technical Specs
Target gas Combustible gases and Toxic gases
Sample manner Natural diffusion
Sensor type Catalytic gas sensor for combustible gas, PID for VOC, Electrochemical gas sensor for toxic gas, infrared for CO₂
Unit %LEL, ppm, %VOL
Response time < 20s
Load resistance (4-20mA) ≤ 250 Ω
Accuracy F.S. ±3%
Repeatability F.S. ≤1%
Working voltage DC24V ±15%
Working condition Combustible gas: Temp. -40°C ~ 70°C
Toxic gas: Temp. -20°C ~ 50°C
Hum. ≤95%RH, no condensation
Explosion-proof ExdⅡCT6
Protection degree IP65
Power Consumption <3W
Cable ≥ RVVP 1.5 mm² × 3
Transmit distance ≤ 1000m
Pressure 86kPa ~ 106kPa
Output signals 4–20mA, Two level free contact (0.5A/AC220V)
Install screw thread G3/4
Colour Yellow
Weight 1600g
Shell Material Aluminum
Name

Related Products